Vertiv / UPS Power & Backup Systems

EXS 0060kBCB01 Equipment information & support

High-reliability online double-conversion high-frequency Uninterruptible Power Supply (UPS) delivering zero-millisecond pure sine wave power to critical IT loads.

Equipment information

Brand
Vertiv
Equipment model
EXS 0060kBCB01
Equipment type
UPS Power & Backup Systems
Controller / software version
Confirm against the installed equipment
View full product specifications
Vertiv EXS 0060kBCB01 Industrial Precision UPS Distribution Cabinet (60kVA BCB Integrated Switchgear) - Internal Assembly & Breaker Configuration

Information below comes from the current product catalogue. Confirm the controller, software version and configuration of the installed equipment separately.

Rated Distribution Capacity
60kVA / 60kW Industrial Rating
Nominal Voltage Specification
380V / 400V / 415V AC (3-Phase 5-Wire)
Core Switchgear Architecture
High-Breaking MCCB + Electronic Trip
Ingress Protection Rating
IP20 (Cold-Rolled Steel Powder-Coated)
Cabinet Dimensions
2000×600×800mm
Maintenance Bypass Switch
Rotary Manual Maintenance Bypass

Alarms & troubleshooting

AC_IN_FAIL / MAINS_LOST
Input Amber / Alarm Red solid
Utility grid failure, AC breaker tripped, or line voltage out of range
1. Measure incoming AC voltage with a multimeter; 2. Check input circuit breaker and upstream distribution; 3. System automatically soft-starts upon power restoration.
DC_OV_SHUTDOWN / LOCKOUT
Alarm Red solid, module output locked out
DC bus overvoltage or internal feedback sensor fault
1. Measure actual DC bus terminal voltage; 2. Cycle AC supply breaker to discharge capacitors and reboot; 3. Replace power module if fault recurs persistently.
FAN_FAIL / OVER_TEMP
Temp Yellow solid, fan halted or derated
Air intake dust blockage or fan bearing obstruction
1. Clean dust accumulation from intake grilles and filters; 2. Verify ambient room air conditioning is operational; 3. Replace cooling fan if rotation remains stalled.

Access Complete Maintenance & Full Alarm Troubleshooting Manual

This page lists high-frequency critical alarm codes commonly encountered in field maintenance. Comprehensive manufacturer troubleshooting matrices, board-level repair guides, detailed electrical schematics, and firmware commissioning manuals are delivered alongside equipment upon formal project procurement, accompanied by dedicated FAE technical support.

Share on-site information

  1. 01

    Identify the exact model

    Record the nameplate, system model and controller or module model.

  2. 02

    Keep the alarm details

    Record the full alarm text, indicator colour, timing and whether it persists.

  3. 03

    Describe recent changes

    Note recent replacements, software updates or configuration changes.

Record information visible in the existing interface. Electrical measurements, disassembly and replacement should follow the applicable manufacturer's manual and be performed by qualified personnel.

Your model and these details will be added to the enquiry form for you to review before sending.

Related technical articles

Browse the technical guides or send a question about this model.

View all articles

Need a replacement module or supporting equipment?

Confirm the full model, system configuration and compatibility requirements before enquiring about suitable products.

Ask about suitable products

Have a model and an on-site issue?

Share the exact model, alarm text and observed symptoms to help identify relevant information and compatibility requirements.

Request technical support