Vertiv / Inverter Systems (DC/AC)

I230-1200 Equipment information & support

The Vertiv I230-1200 is a carrier-grade rack-mounted pure sine wave industrial inverter module engineered for telecommunications and mission-critical power architectures. Operating from a nominal 48V DC bus (40V to 60V DC input range), it delivers a regulated 230V AC ±2% pure sine wave output with a continuous rated capacity of 1200VA / 1000W, featuring true hot-swappable capability and N+1 parallel redundancy support.

Equipment information

Brand
Vertiv
Equipment model
I230-1200
Equipment type
Inverter Systems (DC/AC)
Controller / software version
Confirm against the installed equipment
View full product specifications
Vertiv I230-1200 Genuine Telecom Hardware Shot 2

Information below comes from the current product catalogue. Confirm the controller, software version and configuration of the installed equipment separately.

Cooling Method
Temperature-Controlled Front-to-Rear Airflow
DC Input Voltage
48V DC (40V~60V DC)
Rated Output Power
1200VA / 1000W
AC Output Voltage
-48VDC (-42V ~ -58V)
Maximum Efficiency
≥ 92.0%
Operating Temperature Range
-40°C ~ +75°C

Alarms & troubleshooting

AC_IN_FAIL / AC_DERATE (AC Input Abnormal / Loss / Voltage Derating)
Power LED (Green) OFF or flashing; Protection LED (Yellow) steady ON; Fault LED (Red) OFF.
Utility grid blackout, phase loss, loose terminal screws, or AC input voltage out of operational window (<85VAC derating/cutoff, >295VAC OVP trip).
1. Measure L-N AC voltage at module slot with True-RMS multimeter; 2. Verify AC supply is within nominal range (85~295VAC); 3. Inspect upstream branch circuit breaker (MCB); 4. Retorque wiring terminals and verify neutral connection; 5. If voltage is nominal but yellow LED persists, reseat module and inspect connector pins; replace module if defective.
DC_OV_LOCKOUT / HVSD (DC Output Overvoltage Lockout / HVSD)
Power LED (Green) OFF; Fault LED (Red) steady ON (latched); Protection LED (Yellow) OFF.
Internal PWM loop failure, optocoupler feedback breakdown, or DC bus transient exceeding hardware HVSD threshold (~59.5VDC ±0.5V). Latches off to protect telecom equipment.
1. Extract faulted rectifier and trip its AC feed; 2. Wait at least 3 minutes to discharge internal bus capacitors; 3. Reseat module firmly and power up for a cold restart; 4. Check controller float/equalize target voltage settings (<58.5VDC); 5. If red LED immediately latches on restart, internal regulation failed; replace unit.
OTP_DERATE / OTP_SHUTDOWN (Over-Temperature Derating & Thermal Shutdown)
During derating: Green Power ON, Yellow Protection ON; Thermal shutdown: Green OFF, Yellow ON, Red Fault ON.
Ambient temperature exceeds 55°C, clogged dust filters, air recirculation, or heatsink thermistor (NTC) detecting internal power semiconductor temperature exceeding safety threshold (>105°C).
1. Check site air conditioning and ensure subrack intake air is <35°C; 2. Clean cabinet intake air filters; 3. Install blanking panels in unpopulated slots to eliminate hot air loops; 4. Allow module to cool and verify automatic recovery; 5. If ambient is cool and fan spins but alarm recurs, replace module.
COMM_FAIL / CAN_BUS_LOST (Rectifier CAN Bus Comm Lost / Offline)
Yellow Protection LED flashing (~1Hz); Green Power LED steady ON; Rectifier maintains default float voltage autonomously.
Loose CAN bus flat cable, dirty backplane connector pins, missing or damaged 120-ohm bus termination resistor, or slot address conflict.
1. Reseat module and confirm it latches completely into backplane; 2. Measure equivalent resistance across CAN_H and CAN_L (should read 55~65 ohms with two 120-ohm terminators in parallel); 3. Inspect communication ribbon cable between controller and subrack; 4. Run 'Module Rescan & Auto-Addressing' on controller LCD; 5. If only one slot fails, inspect backplane connector pins.

Access Complete Maintenance & Full Alarm Troubleshooting Manual

This page lists high-frequency critical alarm codes commonly encountered in field maintenance. Comprehensive manufacturer troubleshooting matrices, board-level repair guides, detailed electrical schematics, and firmware commissioning manuals are delivered alongside equipment upon formal project procurement, accompanied by dedicated FAE technical support.

Share on-site information

  1. 01

    Identify the exact model

    Record the nameplate, system model and controller or module model.

  2. 02

    Keep the alarm details

    Record the full alarm text, indicator colour, timing and whether it persists.

  3. 03

    Describe recent changes

    Note recent replacements, software updates or configuration changes.

Record information visible in the existing interface. Electrical measurements, disassembly and replacement should follow the applicable manufacturer's manual and be performed by qualified personnel.

Your model and these details will be added to the enquiry form for you to review before sending.

Related technical articles

Browse the technical guides or send a question about this model.

View all articles